CAUTION
- Air conditioning refrigerant or lubricant vapour can irritate your eyes, nose or throat.
- Be careful when connecting service equipment.
- Do not breathe refrigerant or vapour.
- Use only a gauge set for refrigerant HFC-134a (R-134a).
- Use a vacuum pump adapter which is equipped with a check valve to prevent the backflow of the vacuum pump oil.
|
If accidental system discharge occurs, ventilate work area before resuming service.
Additional health and safety information may be obtained from the refrigerant and lubricant manufacturers.
- When an A/C System has been opened to the atmosphere, such as during installation or repair, it must be evacuated using a R-134a refrigerant vacuum pump. (If the system has been open for several days, the receiver/dryer should be replaced.)
- Connect the R-134a gauge set, pump and refrigerant containers (cans of R-134a) as shown. Do not open the cans.
THREE VALVE GAUGE:
- LOW-PRESSURE VALVE
- EVACUATION VALVE
- HIGH-PRESSURE VALVE
- VACUUM PUMP
- HIGH-PRESSURE QUICK JOINT
- LOW-PRESSURE QUICK JOINT
- CHECK VALVE
| |
TWO VALVE GAUGE:
- LOW-PRESSURE VALVE
- HIGH-PRESSURE VALVE
- EVACUATION STOP VALVE
- VACUUM PUMP
- HIGH-PRESSURE QUICK JOINT
- LOW-PRESSURE QUICK JOINT
- CHECK VALVE
- Start the pump, then open both pressure valves and the evacuation valve (two valve gauge: evacuation stop valve). Run the pump for about 15 minutes.
- Close both pressure valves and the evacuation valve (two valve gauge: evacuation stop valve) and stop the pump. The low-pressure gauge should indicate above 93.3 kPa (700 mmHg, 27.6 in Hg) and remain steady with the valves closed.
- If the low pressure does not reach more than 93.3 kPa (700 mmHg, 27.6 in Hg) in 15 minutes, there is probably a leak in the system. Check for leaks and repair (see page 21-97).
- If there are no leaks, open the valves and continue pumping for at least another 15 minutes. Then close both valves and stop the pump.
|